Data Center Power & Operating Cost Calculator

Estimate a data center’s power and running cost — from a small server room to a 100,000-GPU AI cluster: electricity per year, cost per hour and per GPU, PUE overhead, homes-equivalent, and hardware and other costs.

Tesla’s Cortex cluster started with about 50,000 H100s.
%
Share of maximum power drawn on average.
Total facility power ÷ IT power. Industry average ≈ 1.54; Google’s fleet ≈ 1.09; a typical office server room is often 1.8–2.0.
¢/kWh
U.S. average 2025: industrial 8.62¢, commercial 13.41¢ (EIA).
$
Servers, GPUs, storage and network equipment.
years
$

Results

Electricity cost per year
$50.1 million
Average power drawn by the whole facility
66.3 MW
Electricity per year
580.8 GWh
Electricity cost per hour
$5,715
Share used by cooling and power losses
23.1%
Same electricity as
≈ 55,313 U.S. homes
Electricity per GPU per year
$1,001
💡 GPU power uses the maximum system draw (DGX H100: 10.2 kW per 8 GPUs; GB200 NVL72: about 120 kW per 72 GPUs) scaled by your average load.
💡 Doesn’t include the cost of building the facility, demand charges or taxes. For cooling water, use the data center water calculator.

Formula

Facility power = IT load × utilization × PUE; energy per year = power × 8,760 h; electricity cost = energy × price; total = electricity + hardware ÷ years of use + other costs

Rules of thumb

  • Lowering PUE from 1.5 to 1.2 cuts the facility’s electricity by 20% with the same computers.